  • What is the voltage for VLF cable test?

    그만큼VLF cable tester under Wuhan UHV can help many power workers conduct various power tests more conveniently.


    187


    Core Voltage Parameters


    1.Base Standard:
    VLF testing applies 0.1 Hz AC high voltage at 2 to 3 times the cable’s rated voltage (U₀).
    Examples:
    10 kV rated cable → Test voltage: 22–28 kV (typically 28 kV).

    35 kV rated cable → Test voltage: 70–105 kV (commonly 52–65 kV, subject to standards).


    2.Calculation Basis:
    Formula: Test voltage = (2.0 ~ 3.0) × Rated Voltage (U₀).
    International Standards:
    IEEE 400.2: Mandates 2U₀ for 15 minutes or 3U₀ for 30 minutes.

    IEC 60502-2: Requires 3U₀ for new cables; diagnostic tests on aged cables may use 2U₀.


    3.Safety Limits:
    Never exceed 3U₀: Higher voltages risk damaging healthy insulation.

    XLPE Cable Protection: 0.1 Hz polarity reversal prevents space charge buildup, ensuring test safety.


    Special Scenario Adjustments


    Aged/Damaged Cables: Voltage may be reduced to 1.6U₀ (supported by tanδ diagnostics).
    Post-Repair Verification: 2U₀ for 15 minutes (per IEEE 400.2).
    Note: Actual voltages must align with cable type (XLPE/EPR/PILC), service age, and local standards (e.g., GB/T 12706.4).