qiao@hvtest.cc15871365102
  • UHV(L) 인덕턴스 조정 가능한 전력 주파수 AC 공진 테스트 시스템

    UHV(L) 시리즈 인덕턴스 조정 가능한 전력 주파수 AC 공진 테스트 시스템은 주로 250MW 이하의 유압 발전기 및 기타 전기 기기 등에 대한 내전압 테스트를 수행합니다. 시스템은 주로 AC 전원, 전압 조정기, 여자 변압기, 고압 변압기로 구성됩니다. 전압 리액터, 고전압 분배기 등

    UHV(L) 인덕턴스 가변 전력 주파수 AC 공진 테스트 시스템의 제품 세부 정보


    UHV(L) Power Frequency Series Resonant System

    23

    The UHV(L) Power Frequency Series Resonant Test System is designed for AC withstand tests on single hydro-generators with a capacity of 250MW or less. This system delivers an output voltage waveform with a distortion rate (THD) superior to all existing AC withstand voltage devices, effectively preventing flashover or breakdown and automatically extinguishing arcs after flashover. The main unit of the power frequency withstand voltage tester features large output capacity while requiring only a small power supply.




    The UHV(L) Power Frequency Series Resonant Test System operates on the principle of series resonance, where the inductive reactance of its reactors is tuned to match the capacitive reactance of the test object (e.g., generator windings), creating resonance at power frequency. This allows the system to generate high output test voltages while drawing minimal input current, making it highly efficient.

    1



    Key advantages include:

    High efficiency and low input power requirement due to resonance;

    Superior output waveform quality with low distortion (THD);

    Automatic arc extinguishing and protection against flashover or breakdown;

    Portable and adaptable design, suitable for on-site testing.


    This system offers a reliable, energy-saving solution for high-voltage diagnostic testing in power generation and transmission applications.



    제품 매개변수


    기술적인 매개변수

    정격 출력 전압0 ~ 60kV(AC RMS) and below
    출력 주파수50Hz
    Resonance voltage waveform순수 사인파, 파형 왜곡률 ≤1%
    업무 시스템Full power conticontrol consolenuous working time of 1min
    quality factor10~40
    최대 테스트 용량3000kVA 이하
    작동 전원 공급 장치380V±15%、Power frequency 50Hz


    Serial product configuration(Scope of application(Ac withstand voltage test for generator or motor with outlet voltage of 20kV or below, test frequency: 50Hz))

    제품 모델control consoleVoltage regulatorreactor(dry)Excitation transformer(dry)전압 분배기적용 범위
    UHV(L)- 200kVA/25kV30kW30kVA(electric)200kVA/25kV Adjustable one30kVA dry30kVhydrodynamo.0.4~1.0μF.(10kV/40MW)
    UHV(L)- 300kVA/50kV60kW60kVA(electric)300kVA/50kV Adjustable one60kVA oil-immersed50kVThermal generator.0.27~0.33μF.(20kV/300MW)
    UHV(L)- 600kVA/50kV60kW60kVA(electric)200kVA/50kV Adjustable one
    400kVA/50kV Adjustable one
    60kVA oil-immersed50kVThermal generator.0.113~0.45μF.(20kV/600MW)
    UHV(L)- 1200kVA/50kV120kW120kVA(induction)200kVA/50kV Fixed two
    800kVA/50kV Adjustable one
    120kVA oil-immersed50kVhydrodynamo.0.6~1.8μF.(20kV/250MW)
    UHV(L)- 2750kVA/55kV300kW300kVA(induction)750kVA/55kV Fixed two
    1250kVA/55kV Adjustable one
    120kVA oil-immersed60kVhydrodynamo.1.6~3.3μF.(20kV/770MW)

    Note: the solution can be customized according to the parameters of test objects


    Capacitance of the power system commonly used hydrodynamo reference table

    hydrodynamoRated Capacity(WM)rated voltage(kV)Phase capacitor(μF)
    72.5~8510.50.694
    125~150/1.8~1.9
    30015.751.7~2.5
    40018.02~2.5
    600/2.1~2.5


    Inductance Adjustable Power Frequency AC Resonance Test SystemInductance Adjustable Power Frequency AC Resonance Test System 3Inductance Adjustable Power Frequency AC Resonance Test System 2


    Compared to traditional power frequency test transformers, its advantages are extremely prominent:

    Firstly, the power capacity requirement is low. When testing a 1km 110kV cable, only a 50kW power supply is needed to replace the traditional 2000kVA test transformer, greatly reducing the on-site power supply pressure;

    Secondly, it has strong portability, with lightweight design of core components and a single weight of ≤ 60kg. It is equipped with mobile rollers and specialized lifting structures, making it suitable for transportation and layout in complex environments such as substations and wind power sites;

    Thirdly, it has a wide range of adaptability. By replacing the reactor module and excitation transformer, it can meet the testing needs of various equipment such as 6-500kV cables, 35-500kVGIS, and 10-500kV transformers;

    Fourthly, it has low operating costs, low reactive power loss in resonance state, energy consumption only 1/30-1/100 of traditional equipment, and simple equipment maintenance, with a service life of over 15 years.


    Typical application scenarios

    AC voltage withstand test for hydroelectric generators: for units with a single capacity of 250MW or less, verify the insulation performance of the stator winding.

    High voltage cable withstand voltage test: applicable to the handover and preventive testing of 6kV~500kV cross-linked polyethylene (XLPE) cables.

    Transformer voltage withstand test: Conduct power frequency voltage withstand test on 6kV~500kV transformers to detect insulation defects.

    GIS and SF6 switch test: Verify the insulation strength of gas insulated switchgear equipment.

    Voltage withstand test of other capacitive equipment, such as busbars, bushings, transformers, and other high-voltage equipment.


    FAQ about AC resonant test systems

    1. What is the purpose of series resonance withstand voltage test?  

    Mainly used to detect the insulation performance of power equipment (such as cables, transformers, GIS, etc.) at specific voltages, discover potential insulation defects, and prevent breakdown during operation.

    2. What are the advantages of series resonance test compared to traditional power frequency withstand voltage test?  

    The series resonance test can achieve high test voltage at lower power supply capacity, with lower requirements for the capacitance of the tested object. The electric field generated during resonance is more uniform, and the "impact" on equipment insulation is relatively small.

    3. What safety precautions should be taken when conducting a series resonance test?  

    Strict testing procedures must be followed, including grounding before testing and keeping personnel away during testing. The device itself should also have comprehensive protection functions.

    4. How to choose a suitable series resonant withstand voltage test device based on the test sample?  

    It is necessary to select the appropriate device model based on the capacitance range of the test sample and the required test voltage level, to ensure that the inductance and compensation capability of the device can meet the requirements.









    당신도 좋아할 수도 있습니다

    • 질문이 있으세요!

      언제든지 주저하지 말고 연락주세요
      문의하기
    • 우리를 방문하세요

      6호관, Optics Valley 광학-기계 산업 단지, 84 Gaoxin 5 Road,
      중국 후베이성 ​​우한시 이스트 레이크 신기술 개발구

    • 이메일을 보내주세요

      qiao@hvtest.cc

    • 전화주세요

      +86-15871365102