qiao@hvtest.cc15871365102
  • UHV-8003 휴대용 초음파 부분방전 검출기

    UHV-8003 휴대용 초음파 부분방전 검출기는 부분방전에 의해 발생된 초음파 신호를 수신하여 변압기, GIS, 모터, 케이블 및 절연체, 가공 케이블 등에서 부분방전이 발생하는 유무와 위치를 판단하는 데 주로 사용됩니다. 주로 구성됩니다. 작성자: 휴대용 초음파 부분 방전 감지기 - 메인 호스트, 접촉 초음파 센서, 고주파

    UHV-8003 휴대용 초음파 부분 방전 검출기의 제품 세부 정보



    UHV-8003 Partial Discharge Detector

    HTY_7649

    Product Introduction

    Partial discharge detector manufactures can be widely used for partial discharge detection in power systems, including insulation state detection of high-voltage and other equipment. The discharge degree of electrical equipment can be measured by the following indicators.

    This product can be widely used in partial discharge detection of power system, including high voltage switchgear, ring network cabinet, voltage / current transformer, transformer (including dry type transformer), GIS, overhead line, cable and other equipment insulation state detection, through the following indicators to measure the discharge degree of electrical equipment

    Partial discharge intensity detection: by measuring the discharge signal in one power frequency cycle, the partial discharge intensity is characterized according to the maximum value (dB) in the discharge pulse sequence

    Partial discharge frequency detection: by measuring the discharge signal in one power frequency cycle, the discharge pulse is extracted and the partial discharge frequency is characterized according to the number of discharge pulses.


    HTY_7580

    Product application

    Power generation and distribution enterprises

    Rail system

    Petrochemical power supply system

    Aerospace testing field

    Automated inspection field


    제품 매개변수

    TEV 측정

    측정 범위0dB-60 dB
    해결0.1dB
    정도±1dB
    사이클당 최대 펄스1400
    측정 주파수 대역3~100MHz

    AE measurement

    측정 범위0dB~60dB
    해결0.1dB
    Frequency Range±1dB
    Frequency Range20~200 kHz

    AA,AA1,AA2 measurement

    측정 범위0dB~60dB
    해결0.1dB
    정도±1dB
    센서 중심 주파수40kHz

    UHF measurement

    감지 빈도300-2000MHz
    측정 범위0-60 dBV
    감광도<1dBm
    센서 주파수 대역300-2000MHz

    HFCT measurement

    센서 전송 임피던스5mV/mA
    감지 빈도1~30MHz
    해결0.1dB
    감광도50pC 이하

    하드웨어

    껍데기ABS
    Screen4.3 inch RGB LCD screen, resolution 800*480
    Sampling accuracy12bit
    Synchronization modeInternal synchronization
    커넥터USB 인터페이스(충전기 입력도 가능)
    3.5mm stereo headphone jack
    외부 센서 입력 인터페이스
    Earphone8 Ω minimum
    SD cardStandard configuration 16G ~ 64G
    내장 배터리3.7V/10000mAh lithium battery
    Operating hoursApproxi. 12 hours
    충전기DC 5V/3A
    작동 온도-20 ~ 50℃
    습기20-85% relative humidity
    Volume and weight210*100*35(mm) 0.4KG(host)
    제품 특징

    1、Configure different sensors to realize the partial discharge detection of almost all high-voltage electrical equipment;

    2、Provide a variety of discharge patterns such as time-domain waveform, PRPD, PRPS, etc., to realize the analysis of different discharge types;

    3、Humanized man-machine interface facilitates data management of different devices;

    4、Built-in ultrasonic sensor and transient ground voltage (hereinafter referredtoas TEV) sensor, which can be connected to special sensors such as transformers, GIS, overhead lines, cables, etc.;

    5、The non-invasive detection method does not require power failure during the test process, and there is no need to configure an additional high-voltage source, whichismore convenient to use than the traditional pulsed partial discharge detector factory;

    6、The test bandwidth range is 30kHz ~ 2.0GHz, which is suitable for the detectionprinciple of various frequency bands


    FAQs:

    Q:What is the UHV-8003 Handheld Ultrasonic Partial Discharge Detector? 

    A:The UHV-8003 is a portable partial discharge detection instrument designed to detect and analyze partial discharge signals from high-voltage electrical equipment. It can be used for equipment such as transformers, GIS, motors, cables, insulators, and overhead lines.

    Q:What is partial discharge (PD)? 

    A:Partial discharge is a localized electrical discharge that occurs in part of an insulation system without completely bridging the insulation between conductors. Continuous or severe partial discharge may indicate insulation defects and can contribute to insulation deterioration.

    Q:Can the UHV-8003 perform non-invasive testing? A:Yes. The product uses a non-invasive detection method and is designed to detect partial discharge without requiring an additional high-voltage test source. According to the manufacturer's product information, certain detection applications can be performed without shutting down the equipment.

    Q:How is the UHV-8003 different from a traditional offline partial discharge test system? A:A traditional offline PD test system generally requires a dedicated high-voltage test source and is often used for controlled laboratory or commissioning tests. The UHV-8003 focuses on portable, non-invasive field detection. It can receive PD-related signals without requiring an additional high-voltage source, making it particularly useful for inspection and condition assessment applications.