qiao@hvtest.cc15871365102
  • UHV-220/30F 배터리 방전 테스터 분석기

    UHV-220/30F 배터리 방전 테스터 시스템 단일 배터리의 전압 모니터링 정보는 무선 릴레이 액세스를 통해 간단하고 안전하며 정확합니다. 소리, 빛 경고뿐만 아니라 장비의 명확한 인터페이스 팁까지 완벽한 보호 기능이 있습니다.

    UHV-220/30F 배터리 방전 테스터 분석기의 제품 세부 정보


    Product Introduction

    After years of research and development, our company has successfully developed a series of high-intelligence, high-precision battery discharge testers using our proprietary technology.

    The discharge tester can operate in offline mode, using the battery as the discharge load. By continuously regulating the discharge current, it maintains a constant discharge current at the set value. During discharging, the instrument will automatically stop when any of the following conditions is met: the battery terminal voltage or individual cell voltage falls to the preset lower limit, the set discharge time is reached, or the set discharge capacity is achieved. Throughout the process, all valuable and continuous real-time data is recorded.

    The battery discharge tester system uses wireless relay access to collect voltage monitoring information from individual cells in a simple, safe, and accurate manner.

    The tester features a highly user-friendly interface, allowing users to complete various settings and data queries under menu prompts. Discharge process data can be saved in the device's internal memory and transferred to a USB drive via the data interface. The data can then be analyzed using dedicated PC software to generate required curves and reports.

    The battery discharge tester is equipped with comprehensive protection functions, including audible and visual warnings, as well as clear on-screen interface prompts to ensure safe operation.

    122795-24

    Product functions

    1. Battery capacity testing

    Tests the actual battery capacity (Ah)

    Determines whether the battery meets the rated capacity

    Evaluates the degree of battery aging


    2. Charging test function

    Simulates the actual charging process

    Detects changes in charging voltage and current

    Analyzes battery charging performance


    3. Discharging test function

    Performs constant-current / constant-power discharge on batteries

    Detects the battery's continuous power supply capability

    Verifies the reliability of backup power sources


    4. Battery state of health (SOH) assessment

    Analyzes battery capacity degradation

    Determines the remaining service life of the battery

    Assists in developing maintenance or replacement plans


    5. Battery cycle life testing

    Automatically executes charge-discharge cycles

    Records battery performance changes over time

    Used for battery life verification and R&D testing


    기술적인 매개변수


    작업 모드단독으로 사용 가능, 동시에 사용 가능, 원격 제어 및 상태 모니터링 가능
    Applicable battery48V110V220V380V

    other electrical test

    groups can be customized

    방전 전압0~60V88~132V176V~275V300V~456V
    방전 전류0~150A0~100A0~100A0~30A
    현재의 정확도1%
    전압 정확도0.5%
    모노머 전압 정확도0.2%
    모노머 전압0.500V~16.00V(resolution 1mv)
    충전 방전 시간0 ~ 99시간 59분
    전원공급장치교류:220V
    냉각 방식강제 공랭
    Packagingaluminum alloy pull box


    업무 환경

    열 방출강제 공랭
    온도working range: -5 ~ 50℃ storage temperature: -40 ~ 70℃
    습기relative to humidity0 ~ 90% (40±2℃)
    고도정격 고도: 4000m
    소음﹤60dB


    작동 전원 공급 장치

    전압단상 3선식 : 220V AC (- 20% ~ +30%), 주파수 : 45 ~ 65Hz
    내전압 시험입력 - 하우징: 2200V DC 1분
    입출력: 2200V DC 1분
    출력 - 하우징: 700V DC 1분
    보안EN610950을 충족


    배선

    AC 입력Gb socket, suitable for 1 ~ 1.5mm2케이블
    DC 출력instrument 25 mm2Cable quick connect plug (red positive black negative)


    Product Characteristics

    Constant Current Discharge Function: Continuously adjustable current enables accurate battery capacity measurement.

    Wireless Cell Voltage Monitoring: Each wireless monitoring module can simultaneously monitor up to 12 individual cells.

    PC Analysis Software with Remote Control: Includes Chinese-language background analysis software and supports remote-controlled discharge functionality.

    Data Interface & Storage: The host is equipped with a USB interface and 2GB of high-capacity internal data storage.

    Dual CPU Operation: Dual processors work together to ensure test safety, reliability, and accuracy.

    Flexible Discharge Control: Discharge can be paused and parameters modified without terminating the discharge test.


    Application Scenarios

    Substations

    Testing the capacity and state of health (SOH) of DC screen battery banks

    Used for periodic battery maintenance and acceptance testing


    Power plants

    Testing the performance of backup power batteries at power stations

    Ensuring reliable power supply during emergency situations

    Telecom base stations / communication rooms

    Testing the capacity of communication backup batteries

    Ensuring operation of communication equipment during power outages


    Data centers / UPS rooms

    Testing the discharge capability of UPS battery banks

    Preventing backup power failure

    New energy storage power stations

    Testing the performance of energy storage battery clusters

    Used for lithium battery capacity and cycle life testing


    Battery manufacturers

    Used for factory testing of cells, battery modules, and PACKs

    Performing charge-discharge cycle testing

    New energy vehicle industry

    Testing the performance and degradation of power batteries

    Used for battery maintenance and R&D analysis

    Research institutions / laboratories

    Used for new battery R&D and performance research


    FAQs

    Q: Why is battery charge-discharge testing necessary?

    A: Through testing, it is possible to:

    Determine whether the actual battery capacity meets the specified standards

    Identify batteries with capacity degradation

    Prevent backup power failures in advance

    Extend battery service life

    Improve the reliability of the power supply system


    Q: Can the battery charge-discharge tester determine whether a battery needs to be replaced?

    A: Yes. Through capacity testing, discharge curve analysis, and performance data evaluation, it can determine whether the battery has experienced capacity degradation, aging, or performance abnormalities, thereby assisting in the decision of whether replacement is necessary.


    Q: Why is a battery charge-discharge tester needed in substations?

    A: The DC system in substations relies on batteries to provide backup power. Through charge-discharge testing, it can be confirmed whether the battery bank has the reliable power supply capability required during power outages or emergency situations.


    Q: Why do batteries require periodic discharge testing?

    A: Under long-term floating charge conditions, batteries may experience issues such as capacity degradation and plate sulfation. Regular discharge testing can identify potential problems in advance.


    Maintenance and after-sales service
    Possible field failures
    Voltage alarm: after connecting the large current wire, the machine keeps alarms to check whether the positive and negative poles and the voltage range are within the rated voltage range of the nameplate.
    During the discharge process, the "discharge current fault air switch is abnormal" is displayed.
    Check whether the discharge switch has been closed.
    The discharge current is normal during the discharge process, but the voltage does not drop. The battery pack may not leave the UPS charging system.
    Discharge: the total voltage is not collected, the total voltage acquisition line is not connected, or the reverse, or the line in the middle of the collection line.
    Optional: the single voltage on the site is not consistent with the site, please check whether the wiring harness of the wireless acquisition box is wrongly connected. Generally, the wrong cross connection will show abnormal voltage values such as 5V, 17V. The field wireless single collection voltage collection is not normal, please check the multimeter, or check whether the wiring is wrong. And the actual battery number (some factory battery pack standard number, not according to the actual series sequence number.)


    after-sale service

    The company has a one-year warranty for the products sold(if the contract is not guaranteed separately, the contract shall prevail). Please contact the after-sales service department for your customer maintenance.
    Maintenance cost receivable for any of the following conditions during the warranty period:
    1. Failure or damage caused by impact during user use or handling.
    2. The user is not properly keep, resulting in water seepage, moisture, impact or fire, etc.
    3. Fault or damage caused by maintenance by users or by other units.
    4. Equipment is faulty or damaged due to wiring error.
    5. such as force majeure (such as fire, flood, natural disaster, etc.).
    6. Fault or damage caused by not connecting other equipment according to the requirements of the instructions.
    7. No product warranty card and can not confirmthat the instrument is in the warranty period of the fault products.