  • UHV-520 오프라인 전원 케이블 식별 테스터

    UHV-520 Off line Power Cable Identification Tester is mainly used to accurately identify one of the target cables from multiple cables to avoid serious accidents caused by missawing live cables.

    UHV-520 오프라인 전원 케이블 식별 테스터의 제품 세부 정보

    Product Introduction:

    Wuhan UHV Power Technology Co.,Ltd., is a professional manufacturer and supplier of high-voltage power testing equipment in China.The Cable Identification Instrument is specifically designed for power cable engineers and field workers to solve the technical challenges associated with accurate cable identification. This instrument enables users to reliably identify a target cable from a group of multiple cables, preventing serious accidents caused by mistakenly cutting live cables.

    Cable identification requires coordinated operation at both ends of the cable, and the numbering at both ends must be verified for accuracy. This instrument utilizes advanced PSK technology to ensure precision and reliability. No matter how reliable the memory of field personnel may be, it cannot substitute the certainty provided by a professional instrument.

    Important: This product is intended solely for the on-site identification of power cables that have been de-energized and disconnected. It is strictly prohibited to connect this cable identification device to any live or operating power cable.

    The instrument system consists of a transmitter, a receiver, and a flexible current clamp.

    HTY_8572-2HTY_8622-2


    Product functions:

    1. Accurate cable identification — Locating the designated target cable among a group of multiple cables is its core function.

    2. Pulse-coded signal identification — The transmitter generates a special pulse-coded current to the target cable, and the receiver determines whether it is the target cable by identifying this signal.

    3. Target / non-target cable differentiation — The receiver uses color dynamic indication: target cable shows green clockwise dynamic indication, while non-target cables show red counterclockwise dynamic indication.

    4. Signal strength display — The color dynamic raster displays the strength of the identification signal, assisting in judging the detection status.

    5. AC voltage measurement — The receiver can also measure AC voltage, with a range of 0.01 to 600 V AC and accuracy of ±1% ± 1 digit.

    6. Flexible current clamp detection — Uses a Rogowski flexible coil that can be wrapped around thicker or irregularly shaped cables to detect pulse current.

    7. Rapid on-site testing — Both transmitter and receiver are powered by lithium batteries, providing approximately 8 hours of continuous operation on a full charge.


    Product Characteristics:

    1、Integrated Transmitter Design: The transmitter is housed in a specially designed, integrated toolbox-style enclosure. It is injection-molded using polypropylene plastic reinforced with new composite filling materials. This construction results in low density while offering superior strength, rigidity, hardness, wear resistance, heat resistance, and insulation performance.

    2、Flexible Current Clamp: The flexible current clamp utilizes a Rogowski coil with excellent transient tracking capability. It can quickly and accurately identify the pulse-coded current generated by the transmitter, making it ideal for use with thick cables or conductors with irregular shapes.


    Technical parameters:

    Base conditions and working conditions

    Amount of influenceBenchmark conditionsThe working conditionsnote
    환경 온도23℃±1℃-10℃~40℃/
    Wet environment crossing40%~60%<80%/
    Voltage frequency under test50Hz±1Hz10Hz~1000Hz/
    Receiver operating voltage7.4V±0.5V7.4V±1V/
    Transmitter operating voltage11.1V±0.5V11.1V±1.5V/
    External electric field and magnetic fieldShould be avoided

    Position of cable under testThe cable under test is located at the approximate geometric center of the flexible coil


    Transmitter specification

    Can workGenerating pulse coded current signal;Display remaining battery voltage
    Electrical source11.1v large-capacity rechargeable lithium battery, which works for about 8 hours on full charge
    Pulse voltage500V
    Pulse currentMaximum 30A (depending on the circuit resistance)
    Pulse frequency1 times per second
    The pulse width2ms
    작동 온도-10℃~40℃
    보관 조건-20℃~50℃,≤95%RH, No condensation
    크기320mm×275mm×145mm
    LCDsize128mm×75mm
    LCDAccording to the domain124mm×67mm
    Transmitter mass2.5kg
    The total quality3.3 kg(Contains the receiver)


    Receiver specification

    기능Identify and decode pulse current signals;Ac voltage measurement
    전원 공급 장치7.4v large capacity rechargeable lithium battery, USB charging interface, full charge continuously working for about 8

    시간

    정격 전류about 180mA max
    디스플레이 모드3.5 "true color LCD display, color electronic dial indicator
    Cable identification successfulGreen grating clockwise dynamic indicator
    Non-target cableRed grating counterclockwise dynamic indication
    Receiver size207mm×101mm×45mm
    Flexible coilIt is about 630mm in length and 6mm or 12.5mm in diameter
    Coil diameterφ200mm
    Detection rangeCoil loop resistance can be detected to 0 Ω ~ 2 k Ω pulse signal;When detecting circuit resistance for the 2 k Ω, need

    to ensure the transmitter battery for more than 10v

    전압 범위AC 0.01V~600V(50Hz/60Hz)
    전압 정확도±1%±1dgt
    Identification signalColor grating dynamic display of signal strength
    Detection rateAbout 1 time/second
    The battery voltageWhen the battery voltage is lower than 6.5V, the battery voltage depression symbol is displayed to remind the

    battery to charge

    Operating temperature and humidity-10℃~40℃;80%RhThe following
    Storage temperature and humidity-10℃~50℃,≤95%RH, No condensation
    Receiver mass370g(with battery)
    Current clamp mass172g


    애플리케이션Scenarios

    Substation and distribution room maintenance

    Used to confirm the target cable when there are a large number of cables on site, labels are unclear, or the as-built drawings are inconsistent with the actual conditions.

    Cable trenches and cable tunnels

    Suitable for locations where cables are laid in concentrated areas. Each cable can be tested individually to determine which one is the target cable.

    Cable relocation projects

    During construction work such as road widening, subway construction, or utility tunnel development, when underground cables need to be relocated or removed, the target cable can be confirmed first.

    Old cable removal

    Used to confirm decommissioned cables during retrofitting of old substations, factories, and other facilities, reducing the risk of mistakenly cutting live or in-service cables.

    Cable fault maintenance

    After the fault location has been determined using cable fault locating equipment, the specific cable can be further confirmed to facilitate subsequent excavation and repair work.

    Power plants and industrial enterprises

    Used for equipment retrofitting, outage maintenance, line upgrades, and organization of legacy cable records.

    Cable construction and acceptance

    Can be used to confirm the correspondence between cable ends at both sides, helping construction personnel verify cable numbers and actual routing.


    FAQ about Cable Identification Instrument

    Q: How does it identify the target cable?

    A: The device applies a specific pulse-coded signal to the target cable through the transmitter. The receiver uses a flexible current clamp to detect this signal, thereby determining whether the cable currently being tested is the target cable.

    Q: Can it still identify the cable when there are many cables?

    A: Yes. The device is designed specifically to locate the target cable among multiple cables. On site, each cable can be tested one by one according to the cable arrangement, and the target cable can be confirmed at the end.

    Q: Why is it necessary to use the transmitter and receiver together?

    A: Because the device needs to establish a clear correspondence between the target cable, the identification signal, and the receiver. This prevents misjudgment that may occur when relying solely on ordinary current or voltage measurements.