qiao@hvtest.cc15871365102
  • UHV-801 Ground Network Earth Resistance Tester

    Ground Network Earth Resistance Tester revolutionizes earth grid resistance measurement in power systems by replacing traditional 30A power-frequency methods with frequency-conversion AC technology and microprocessor control.

    Product Details of UHV-801 Ground Network Earth Resistance Tester


    Product Introduction

    This UHV-801 Ground Network Earth Resistance Tester utilizes frequency-conversion technology and microprocessor control to accurately measure grounding resistance (4Ω-10Ω), contact/step voltage, and soil resistivity. Featuring 50Hz anti-interference capability and 3A test current, it enables reliable live-grid testing without power outages. The compact design significantly improves efficiency, reducing testing time and labor intensity compared to traditional 30A methods. Suitable for substations, power plants, and lightning protection systems.



    Key Features of Ground Grid Resistance Tester:

    1、Precision Power Frequency Simulation - Delivers accurate sinusoidal waveforms with ±5Hz frequency variation (45Hz/55Hz), ensuring power frequency equivalence in measurements.

    2、Advanced Anti-Interference Technology - Combines variable frequency measurement with digital filtering for stable, reliable data even in high-noise environments.

    3、Exceptional Accuracy - Achieves 0.005Ω basic error resolution, capable of testing low-impedance grounding systems with precision.

    4、Comprehensive Measurement Capabilities - Tests current/voltage poles, grounding resistance, step voltage, and contact voltage in one integrated solution.

    5、User-Friendly Interface - Features intuitive Chinese menu navigation with direct measurement readouts for simplified operation.

    6、Efficient Field Operation - Eliminates heavy cabling requirements with compact design that doesn't require high-current lines.


    Technical Advantages:

    • True power frequency simulation

    • Superior noise rejection

    • Micro-ohm resolution

    • Multi-parameter testing

    • Simplified workflow

    • Lightweight field deployment


    Technical parameter

    measurement range:0~200Ω(현재 파일 임피던스 포함)

    해결: 0.001Ω

    측정 오류: ±(readings×1%+0.005Ω)

    최대 출력 전압: AC 400V (45Hz, 55Hz, dual-frequency, sine wave)

    maximum output current: AC 5A(45Hz, 55Hz, 이중 주파수, 사인파)

    출력기어: 5 / 4.5/4/3.5/3/2.5/2/1.5/1a, every 0.5A, 9 gears in total

    간섭 방지 능력: anti-power frequency 50Hz voltage 10V

    measurement line requirements:   Section area of copper core of current wire ≥ 1.5mm2

                                                                Sectional area of copper core of voltage line ≥ 1.0mm2

    power supply: AC220V±10%,50Hz

    External dimension: 295×340×310mm3

    instrument weight: 30kg








    당신도 좋아할 수도 있습니다

    • 질문이 있으세요!

      언제든지 주저하지 말고 연락주세요
      문의하기
    • 우리를 방문하세요

      6호관, Optics Valley 광학-기계 산업 단지, 84 Gaoxin 5 Road,
      중국 후베이성 ​​우한시 이스트 레이크 신기술 개발구

    • 이메일을 보내주세요

      qiao@hvtest.cc

    • 전화주세요

      +86-15871365102