  • UHV-H100P 접촉 저항 테스트 루프 저항 테스터

    UHV-H100P는 고전압 및 저전압 스위치 접점(루프) 저항, 고정밀 측정의 케이블 라인 DC 저항 값에 적합하며 다른 요구 사항인 대전류, 마이크로 저항 측정 경우에도 적합합니다.

    UHV-H100P 접촉 저항 테스트 루프 저항 테스터의 제품 세부 정보


    Product Introduction:

    At present, the conventional QJ44 double-arm DC bridge is widely used in power system to measure contact resistance, but the testing current of this kind of bridge is only mA level, so it is difficult to find the defect of reducing the cross-sectional area of the loop conductor. When measuring the contact resistance of the conductive circuit of the high voltage switch, due to the influence of the oil film and oxide layer between the contacts, the measured value is several times too large to truly reflect the contact resistance value. To this end, the latest Ministry of Power standard DL/T845.4 -- 2004 "resistance measuring device general technical conditions: Circuit Resistance Tester and the new version of Verification regulation JJG1052-2009 "Circuit Resistance Tester and Direct Resistance Tester Verification Regulation" stipulate that the measuring current of contact resistance such as switch (isolation) and circuit breaker shall not be less than 100A DC and the minimum current maintenance time shall not be less than 60S to ensure the accuracy of test results.

    The instrument operating panel adopts ergonomic design, in line with operating habits, the use of high frequency switching power supply and digital circuit technology, suitable for the measurement of switching control equipment circuit resistance. The test current is 100A DC recommended by the national standard. The circuit resistance can be measured directly under the DC 100A condition, the test results are displayed with a large screen LCD, and has data storage, output printing, time setting and other functions, and another 50A gear for users to choose; Is the only domestic can reach 0.01μΩ resolution and very stable contact resistance tester, performance more than imported large current micrometer. Meet the requirements of high voltage switch maintenance and circuit resistance test in power and power supply departments.


    Application scenarios

    High-voltage circuit breakers: Measuring the contact resistance of their conductive loop is a key indicator for determining whether the contacts are worn, eroded, or have poor contact.

    Disconnecting switches and load switches: Detecting whether the contacts are in good condition to prevent heating faults caused by excessively high contact resistance.

    High- and low-voltage switchgear: Performing periodic preventive tests on the main circuit, busbar connections, and other points within the switchgear.


    Product Features:

    1. High-Current Output

    Utilizing advanced switching power supply technology, the instrument delivers a continuous, high-current output over extended durations. It overcomes the limitations of pulsed power supplies that rely on instantaneous current, effectively penetrating switch contact oxide films to ensure reliable and accurate test results.

    2. Exceptional Stability

    Even under conditions of significant electromagnetic interference, the last digit of the LCD reading remains stable within a range of ±1 count. This ensures highly consistent readings and excellent measurement repeatability.

    3. Superior Precision

    Equipped with dual high-speed 16-bit Σ-Δ AD converters and digital signal processing technology, the instrument achieves a maximum resolution of 0.01 μΩ. It is one of the most stable contact resistance testers available in China with such resolution, delivering performance that surpasses many imported high-current micro-ohmmeters.

    4. Intelligent Operation

    Powered by a high-performance port CPU, the system automatically selects the appropriate measurement range based on signal strength, ensuring optimal accuracy. An integrated over-temperature protection circuit automatically cuts off the output current if the instrument exceeds preset temperature limits, guaranteeing safe operation.

    5. Premium Build Quality

    All critical components are sourced from internationally recognized manufacturers. The device incorporates a sophisticated temperature compensation circuit to minimize the influence of ambient temperature on measurements. Military-grade connectors further enhance durability and vibration resistance.

    6. Advanced Functionality

    Users can freely select test currents of 50A or 100A and set test durations anywhere between 5 and 599 seconds. This addresses the shortcomings of comparable instruments that lack configurable test times or offer limited continuous operation, placing this device far ahead in performance.

    7. User-Friendly Interface

    Data entry is simplified via a rotary mouse, providing quick and intuitive operation. The instrument allows independent setting of date and time, supports real-time data saving, and enables on-demand printing of test results.

    8. USB Data Transfer

    Measurement data can be transferred directly to a USB flash drive via the built-in USB interface. Combined with dedicated PC software, this allows for in-depth analysis and further processing of test data.

    9. Portable Design

    Compact and lightweight, the instrument is easy to transport and ideal for both laboratory and field applications.


    Technical Parameters:

    측정 범위50A 0~10mΩ
    100A 0~5mΩ
    해결0~99.99μΩ, 0.01μΩ
    100.0~10000.0μΩ, 0.1μΩ
    테스트 전류DC50A, 100A 2단 고정 출력
    측정 정확도±(0.5% rd+2d)
    Operating Time OptionsQuick, 10s, 30s, 60s
    표시방법4-inch touchscreen
    통신 모드U 디스크 덤프
    일하는 힘AC220V±10% 50Hz
    총 전력600W
    최대 저장 기록200
    근무 환경temperature: -10℃~40℃, humidity:≤80%RH
    치수390×300×150 mm3
    무게6kg(No attachments)

    FAQ about Contact Resistance Tester

    Q: Why do high-precision loop resistance testers typically use high-current output?

    A: High-precision loop resistance testers output a stable high current to effectively reduce the influence of environmental noise and lead resistance during contact resistance measurement, thereby achieving more accurate test results. A higher test current also more accurately reflects the conductive performance of circuit breakers, disconnecting switches, and busbar connection points under actual operating conditions.

     

    Q: How does the test current level affect the measurement results?

    A: Properly increasing the test current can reduce errors caused by unstable contact resistance and improve the consistency of measurement data. However, the test current should comply with the rated requirements of the equipment to avoid local heating of the device under test or safety risks due to excessive current. In practice, the appropriate test current level should be selected based on the equipment type and industry standards.

     

    Q: How to select a suitable high-precision loop resistance tester for specific application needs?

    A: When selecting a model, factors such as maximum output current, measurement range, resolution, measurement accuracy, data storage capacity, and portability should be comprehensively considered. For long-term on-site testing in substations or large industrial environments, attention should also be paid to the equipment's protection rating, battery life, and software compatibility to meet varying test conditions and future maintenance requirements.